How to choose a sulfur hexafluoride gas analyzer
Product Introduction Comparison of Four SF6 gas analyzer
1.WIKA GA11
2.DILO 3-038R-R403
3.Rapidox SF6 6100
4.SF6Relations RA912F
1.WIKA GA11

Applications of the SF6 Gas analyzer
Special features of the SF6 Gas analyzer
Provides measured values for humidity, gas composition (purity) and decomposition products (optional)
Low transport weight of 25 kg
Three methods for emission-free treatment of the measurement gas:
- Direct pumping back into the tested compartment
- Pumping into an external gas cylinder
- Collecting in an external gas bag
Battery power for min. 5 measurements or mains supply
Not compromised by transport restrictions (IATA)
Inlet/return pumps 1.3 ... 35 bar abs./1.3 ... 10 bar abs.
Outlet for gas cylinder 1.3 ... 10 bar abs.
Outlet for gas recovery bag < 1.015 bar abs.
SF₆ percentage sensor
Measurement principle Sound velocity
Measuring range/accuracy 0 ... 100 % ±0.5 % based on SF₆/N₂ mixtures (calibration for SF₆/CF₄ mixtures on request)
Resolution 0.1 %
Humidity sensor
Measurement principle Polymer-based capacitive humidity sensor
Measuring range/accuracy -40 ... +20 °C dew point ±2 °C
dew point -60 ... < -40 °C dew point ±4 °C dew point
Resolution 1 °C
SO₂ sensor
Measurement principle Electrochemical SO₂ sensor
Measuring range/accuracy In combination with HF sensor, only 0 … 10 or 0 … 20 ppmv make sense.
■ 0 ... 10 ppmv ±0.5 ppmv
■ 0 ... 20 ppmv ±1 ppmv
■ 0 ... 100 ppmv ±3 ppmv
■ 0 ... 500 ppmv ±5 ppmv
Resolution 0.1 ppmv
Service life 2 years starting from installation
H₂S sensor
Measurement principle Electrochemical H₂S sensor
Measuring range/accuracy 0 ... 100 ppmv ±5 ppmv
Resolution 0.1 ppmv
Service life 2 years starting from installation
CO sensor
Measurement principle Electrochemical CO sensor
Measuring range/accuracy 0 ... 500 ppmv ±9 ppmv
Resolution 0.1 ppmv
Service life 2 years starting from installation
Here's the sensor information presented in a table format:
Sensor | Measurement Principle | Measuring Range/Accuracy | Resolution | Service Life |
SF₆ percentage | Sound velocity | 0 … 100% ±0.5% based on SF₆/N₂ mixtures (calibration for SF₆/CF₄ mixtures on request) | 0.1% | 2 years starting from installation |
Humidity | Polymer-based capacitive humidity sensor | -40 … +20°C dew point ±2°C dew point<br>-60 … < -40°C dew point ±4°C dew point | 1°C | - |
SO₂ | Electrochemical SO₂ sensor | 0 … 10 ppmv ±0.5 ppmv 0 … 20 ppmv ±1 ppmv 0 … 100 ppmv ±3 ppmv 0 … 500 ppmv ±5 ppmv | 0.1 ppmv | 2 years starting from installation |
H₂S | Electrochemical H₂S sensor | 0 … 100 ppmv ±5 ppmv | 0.1 ppmv | 2 years starting from installation |
CO | Electrochemical CO sensor | 0 … 500 ppmv ±9 ppmv | 0.1 ppmv | 2 years starting from installation
|
2.DILO 3-038R-R…

DILO 3-038R-R… Selection Table
Device Type | Measurement Capabilities | Range/Specifications | Model |
Single measuring | Percentage Measurement | 0 - 100 vol.-% | R101 |
Single measuring | Moisture Measurement | -76 °F to 68 °F (-60 °C to +20 °C) dew point | R102 |
Two-in-one measuring | Percentage and Moisture Measurement |
| R201 |
Three-in-one measuring | Percentage, Moisture, and SO2 Measurement | 0 - 20 ppm SO2 | R301 |
Three-in-one measuring | Percentage, Moisture, and SO2 Measurement | 0 - 100 ppm SO2 | R302 |
Three-in-one measuring | Percentage, Moisture, and SO2 Measurement | 0 - 500 ppm SO2 | R303 |
Four-in-one measuring | Percentage, Moisture, SO2, and HF Measurement | 0 - 20 ppm SO2, 0 - 10 ppm HF | R401 |
Four-in-one measuring | Percentage, Moisture, SO2, and HF Measurement | 0 - 100 ppm SO2, 0 - 10 ppm HF | R402 |
Four-in-one measuring | Percentage, Moisture, SO2, and HF Measurement | 0 - 500 ppm SO2, 0 - 10 ppm HF | R403 |
Six-in-one measuring | Percentage, Moisture, SO2, HF, H2S, and CO Measurement | 0 - 100 ppm SO2, 0 - 10 ppm HF, 0 – 100 ppm H2S, 0 – 500 ppm CO | R602 |
Sensor | Measuring Principle | Measuring Range | Measuring Accuracy | Adjustable Limit Value | Recommended Calibration Interval |
Purity | Velocity of Sound | 0–100 % vol | ±0.5% vol | 0-100% vol | 2 years |
Moisture | Electronic Dew Point Measurement (Capacitive) | -60 to +20°C | ±2 °C (> -40 °C), ±3 °C (< -40 °C) | -60 to +20 °C | 2 years |
SO2 | Electrochemical Reaction | 0 – 20ppm, 0 –100ppm, 0– 500ppm | < ±2% of Measuring Range | 0 – 20 ppm | 2 years (lifetime) |
CO Option | Electrochemical Reaction | 0 – 500ppm | < ±2% of Measuring Range | 0 – 500 ppm | 2 years (lifetime) |
HF Option | Electrochemical Reaction | 0–10 ppm | < ±10% of Measuring Range | 0 – 10ppm | 2 years (lifetime) |
H2s Option | Electrochemical Reaction | 0–100 ppm | < ±2% of Measuring Range | 0–100ppm | 2 years (lifetime) |
3.Rapidox SF6 6100

The Rapidox SF6 6100 Portable is designed for controlling and monitoring the quality of SF6 in MV & HV gas insulated electrical equipment. Exceptional accuracy and stability are provided when measuring the purity of SF6 gas, through specially selected sensors. A gas output nozzle allows for the analyser to be attached to the Rapidox Gas Recovery Bag, ensuring that all sampled SF6 gas is recovered.

Sensor | Specification | Accuracy | Calibration | Lifespan | Sensor Type |
SF6 (Sulphur Hexafluoride) | 0-100% | ±0.5% accuracy | Every 12 months | >5 years | Infrared (IR) |
H2O (Dew Point) | -60°C to +20°Cdp (10 – 24,000ppmV) | ±2°Cdp of reading | Every 12 months by Sensor Exchange | 2-3 years | Polymer |
SO2 (Sulphur Dioxide) | 0-100ppm OR 0-500ppm | ±2% full-scale | Every 12 months | 2-3 years | Electrochemical |
HF (Hydrogen Fluoride) | 0-10ppm OR 0-30ppm | ±2% full-scale | Every 12 months (Using HCI gas) | 2-3 years | Electrochemical |
CF4* (Tetrafluoromethane) | 0-80% | ±1% of full reading | N/A | N/A | (measured by balance of SF6 + Air reading) |
H2S (Hydrogen Sulphide) | 0-100ppm | ±2% full-scale | Every 12 months | 2-3 years | Electrochemical |
CO (Carbon Monoxide) | 0-1,000ppm | ±2% full-scale | Every 12 months | 2-3 years | Electrochemical |
O2 (Air) / N2 (Nitrogen) | 0-100% | full-scale based on oxygen component | Every 12 months | 2-3 years | Electrochemical O2 scaled to read as Air or Nitrogen |
4.SF6Relations RA912F

The RA912F multi-functional SF6 Gas analyzer allows the determination of up to 6 quality parameters with only one measurement
SF6 concentration (%)
Moisture concentration (Dew Point)
SO2 concentration (ppmv)
CO concentration (ppmv)
H2S concentration (ppmv)
Option: HF concentration (ppmv)
RA-912F SF6 Multi-Analyzer measures SF6 purity based on the principle of thermal conductivity. Its unique spectral band absorption characteristics accurately identify SF6, effectively reducing interference from other components, making it suitable for electrical equipment filled with SF6 and gases like N2 or CF4. The device features an advanced cross-sensitivity decomposition algorithm, built upon extensive laboratory data and incorporating linear algebra for enhanced accuracy. Additionally, it employs the classic polymer film method for measuring SF6 humidity. Changes in
ambient humidity alter the dielectric constant of moisture-sensitive components, thereby causing changes in the output electrical signal.

RA912FP
Besides having the same features as the RA912. RA912FP has a fully automatic SF6 analyzer designed
to meet zero emissions,After measurement, the gas can be pumped back in the original way.
Technical Data |
Dimensions: L 406 mm, W 538 mm, H 269 mm |
Weight: 15 kg |
Input Pressure: 0.2 - 35 bar |
Operating Temperature: -20 °C to +50 °C |
Ambient Moisture: 15% up to 90% relative moisture, non-condensing during operation |
Operating Voltage: 100-240 VAC, 50/60Hz |
Number of Measured Values to be Stored: Max. 500 |
Interface: USB |
Parameter | Purity | Moisture | SO2 | H2S | CO |
Measuring Principle | Thermal conductivity | Electronic moisture measurement (capacitive) | Electrochemical reaction | Electrochemical reaction | Electrochemical reaction |
Measuring Range | 0 - 100 vol.% | -80 to +20 °C | 0 to 100 ppm | 0 to 10 ppm | 0 to 500 ppm |
Measuring Accuracy | ±0.5 % (F.S) | ±2 °C | ±5 % μL/L | ±5 % μL/L | ±5 % μL/L |
Flow Rate | 250 to 350 mL/min Recommend 300 mL/min | 300 to 900 mL/min Recommend 500 mL/min | 100 to 120 mL/min Recommend 100 mL/min | 100 to 120 mL/min Recommend 100 mL/min | 100 to 120 mL/min Recommend 100 mL/min |
Reaction Time | < 30 s | < 3 min | < 60 s | < 60 s | < 60 s |
Recommended Calibration Interval | every one year | every one year | every one year | every one year | every one year |